Application
This robust medium voltage cable is engineered for demanding power distribution applications. Three Core Individually Screened & PVC Sheathed cable is a Medium Voltage (MV) feeder cable primarily used in permanent, fixed installations for electrical power distribution. Its main application is to provide primary power supply from substations or main distribution points to industrial plants, commercial centers, and urban/residential distribution networks.
Applicable Standards
- Structure: AS/NZS 1429.1
- Conductor: AS/NZS 1125
- Sheath: AS/NZS 3808
Construction
- Conductor: Class 2 stranded (compacted) aluminium wire
- Conductor screen: Semi-conductive compound material
- Insulation: XLPE insulation (Colour: Red, White, Blue)
- Insulation screen: Semi-conductive compound material
- Binder tape: Semi-conductive water blocking binder tape
- Metallic screen: HD-Plain annealed copper wire (optional: LD)
- Filler: PP filler (Non-hygroscopic material)
- Wrapping tape: Non-woven tape (Non-hygroscopic)
- Outer Sheath: 5V-90 PVC (optional: HDPE/LSZH) – Colour: Black
Available Voltage Ratings:
- 3.8/6.6kV Three Core
- 6.35/11KV Three Core
- 12.7/22KV Three Core
- 19/33KV Three Core
| Nom. Conductor Area |
Nom. Conductor Diameter |
Nom. Insulation Thickness |
Nom.Dia Over Insulation |
Nom.Screen Area on Each Core |
No.&Dia of Screen Wires |
Nominal Dia over Wire Screen |
Nom. Overall Diameter |
Approx. Weight |
| Nom. Conductor Area |
Nom. Conductor Diameter |
Nom. Insulation Thickness |
Nom.Dia Over Insulation |
Nom.Screen Area on Each Core |
No.&Dia of Screen Wires |
Nominal Dia over Wire Screen |
Nom. Overall Diameter |
Approx. Weight |
| Nom. Conductor Area |
Nom. Conductor Diameter |
Nom. Insulation Thickness |
Nom.Dia Over Insulation |
Nom.Screen Area on Each Core |
No.&Dia of Screen Wires |
Nominal Dia over Wire Screen |
Nom. Overall Diameter |
Approx. Weight |
| mm² |
mm |
mm |
mm |
mm2 |
No./mm |
mm |
mm |
kg/100m |
| Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
| 16 |
4.8 |
2.5 |
11.0 |
17.0 |
10/0.85 |
14.3 |
35.6 |
130 |
| 25 |
5.8 |
2.5 |
12.0 |
25.5 |
15/0.85 |
15.3 |
37.9 |
170 |
| 35 |
6.8 |
2.5 |
13.0 |
34.0 |
20/0.85 |
16.3 |
40.3 |
215 |
| 50 |
8.0 |
2.5 |
14.1 |
49.4 |
29/0.85 |
17.4 |
43.0 |
275 |
| 70 |
9.6 |
2.5 |
15.7 |
68.1 |
40/0.85 |
19.0 |
46.7 |
360 |
| 95 |
11.5 |
2.5 |
17.6 |
68.1 |
40/0.85 |
20.9 |
51.1 |
455 |
| 120 |
13.1 |
2.5 |
19.2 |
68.1 |
40/0.85 |
22.5 |
54.8 |
545 |
| 150 |
14.5 |
2.5 |
20.6 |
68.1 |
40/0.85 |
23.9 |
58.2 |
630 |
| 185 |
16.1 |
2.5 |
22.2 |
68.1 |
40/0.85 |
25.5 |
61.8 |
735 |
| 240 |
18.5 |
2.6 |
24.9 |
68.1 |
40/0.85 |
28.2 |
67.9 |
930 |
| 300 |
20.7 |
2.8 |
27.6 |
68.1 |
40/0.85 |
30.9 |
74.3 |
1130 |
| 400 |
23.6 |
3.0 |
30.9 |
68.1 |
40/0.85 |
34.2 |
81.8 |
1440 |
| Aluminum Conductors,up to 10KA fault level |
Aluminum Conductors,up to 10KA fault level |
Aluminum Conductors,up to 10KA fault level |
Aluminum Conductors,up to 10KA fault level |
Aluminum Conductors,up to 10KA fault level |
Aluminum Conductors,up to 10KA fault level |
Aluminum Conductors,up to 10KA fault level |
Aluminum Conductors,up to 10KA fault level |
Aluminum Conductors,up to 10KA fault level |
| 35 |
6.9 |
2.5 |
13.0 |
23.8 |
14/0.85 |
16.3 |
40.5 |
140 |
| 50 |
8.1 |
2.5 |
14.2 |
32.3 |
19/0.85 |
17.5 |
43.1 |
170 |
| 70 |
9.6 |
2.5 |
15.8 |
46.0 |
27/0.85 |
19.1 |
46.8 |
210 |
| 95 |
11.4 |
2.5 |
17.5 |
61.3 |
36/0.85 |
20.8 |
50.8 |
270 |
| 120 |
12.8 |
2.5 |
18.9 |
68.1 |
40/0.85 |
22.2 |
54.1 |
305 |
| 150 |
14.2 |
2.5 |
20.3 |
68.1 |
40/0.85 |
23.6 |
57.3 |
340 |
| 185 |
15.7 |
2.5 |
21.8 |
68.1 |
40/0.85 |
25.1 |
60.8 |
385 |
| 240 |
18.0 |
2.6 |
24.3 |
68.1 |
40/0.85 |
27.6 |
66.6 |
465 |
| 300 |
20.1 |
2.8 |
27.0 |
68.1 |
40/0.85 |
30.3 |
72.8 |
550 |
| 400 |
23.0 |
3.0 |
30.3 |
68.1 |
40/0.85 |
33.6 |
80.3 |
660 |
| Nom. Conductor Area |
Nom. Conductor Diameter |
Nom. Insulation Thickness |
Nom.Dia Over Insulation |
Nom.Screen Area on Each Core |
No.&Dia of Screen Wires |
Nominal Dia over Wire Screen |
Nom. Overall Diameter |
Approx. Weight |
| Nom. Conductor Area |
Nom. Conductor Diameter |
Nom. Insulation Thickness |
Nom.Dia Over Insulation |
Nom.Screen Area on Each Core |
No.&Dia of Screen Wires |
Nominal Dia over Wire Screen |
Nom. Overall Diameter |
Approx. Weight |
| Nom. Conductor Area |
Nom. Conductor Diameter |
Nom. Insulation Thickness |
Nom.Dia Over Insulation |
Nom.Screen Area on Each Core |
No.&Dia of Screen Wires |
Nominal Dia over Wire Screen |
Nom. Overall Diameter |
Approx. Weight |
| mm² |
mm |
mm |
mm |
mm2 |
No./mm |
mm |
mm |
kg/100m |
| Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
| 16 |
4.8 |
3.4 |
12.8 |
17.0 |
10/0.85 |
16.1 |
40.0 |
150 |
| 25 |
5.8 |
3.4 |
13.8 |
25.5 |
15/0.85 |
17.1 |
42.3 |
195 |
| 35 |
6.8 |
3.4 |
14.8 |
34.0 |
20/0.85 |
18.1 |
44.7 |
240 |
| 50 |
8.0 |
3.4 |
16.0 |
49.4 |
29/0.85 |
19.3 |
47.4 |
295 |
| 70 |
9.6 |
3.4 |
17.6 |
68.1 |
40/0.85 |
20.9 |
51.0 |
390 |
| 95 |
11.5 |
3.4 |
19.4 |
68.1 |
40/0.85 |
22.7 |
55.3 |
480 |
| 120 |
13.1 |
3.4 |
21.0 |
68.1 |
40/0.85 |
24.3 |
58.9 |
575 |
| 150 |
14.5 |
3.4 |
22.4 |
68.1 |
40/0.85 |
25.7 |
62.3 |
665 |
| 185 |
16.1 |
3.4 |
24.1 |
68.1 |
40/0.85 |
27.4 |
66.0 |
770 |
| 240 |
18.5 |
3.4 |
26.5 |
68.1 |
40/0.85 |
29.8 |
71.6 |
965 |
| 300 |
20.7 |
3.4 |
28.9 |
68.1 |
40/0.85 |
32.2 |
76.9 |
1160 |
| 400 |
23.6 |
3.4 |
31.8 |
68.1 |
40/0.85 |
35.3 |
84.2 |
1460 |
| 500 |
26.5 |
3.4 |
34.7 |
68.1 |
40/0.85 |
38.2 |
90.9 |
1790 |
| Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
| 35 |
6.9 |
3.4 |
14.9 |
23.8 |
14/0.85 |
18.2 |
44.6 |
165 |
| 50 |
8.1 |
3.4 |
16.0 |
32.3 |
19/0.85 |
19.3 |
47.5 |
195 |
| 70 |
9.6 |
3.4 |
17.6 |
46.0 |
27/0.85 |
20.9 |
51.1 |
245 |
| 95 |
11.4 |
3.4 |
19.3 |
61.3 |
36/0.85 |
22.6 |
55.0 |
295 |
| 120 |
12.8 |
3.4 |
20.7 |
68.1 |
40/0.85 |
24.0 |
58.2 |
340 |
| 150 |
14.2 |
3.4 |
22.1 |
68.1 |
40/0.85 |
25.4 |
61.5 |
375 |
| 185 |
15.7 |
3.4 |
23.6 |
68.1 |
40/0.85 |
26.9 |
64.9 |
420 |
| 240 |
18.0 |
3.4 |
25.9 |
68.1 |
40/0.85 |
29.2 |
70.3 |
490 |
| 300 |
20.1 |
3.4 |
28.3 |
68.1 |
40/0.85 |
31.6 |
75.5 |
570 |
| 400 |
23.0 |
3.4 |
31.1 |
68.1 |
40/0.85 |
34.6 |
82.8 |
690 |
| 500 |
26.5 |
3.4 |
34.7 |
68.1 |
40/0.85 |
38.2 |
90.9 |
845 |
| Nom. Conductor Area |
Nom. Conductor Diameter |
Nom. Insulation Thickness |
Nom. Dia Over Insulation |
Nom. Screen Area on Each Core |
No.&Dia of Screen Wires |
Nominal Dia over Wire Screen |
Nom. Overall Diameter |
Approx. Weight |
| Nom. Conductor Area |
Nom. Conductor Diameter |
Nom. Insulation Thickness |
Nom. Dia Over Insulation |
Nom. Screen Area on Each Core |
No.&Dia of Screen Wires |
Nominal Dia over Wire Screen |
Nom. Overall Diameter |
Approx. Weight |
| Nom. Conductor Area |
Nom. Conductor Diameter |
Nom. Insulation Thickness |
Nom. Dia Over Insulation |
Nom. Screen Area on Each Core |
No.&Dia of Screen Wires |
Nominal Dia over Wire Screen |
Nom. Overall Diameter |
Approx. Weight |
| mm² |
mm |
mm |
mm |
mm2 |
No./mm |
mm |
mm |
kg/100m |
| Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
| 35 |
6.8 |
5.5 |
19.1 |
34.0 |
20/0.85 |
22.4 |
54.6 |
300 |
| 50 |
8.0 |
5.5 |
20.3 |
49.4 |
29/0.85 |
23.6 |
57.3 |
360 |
| 70 |
9.6 |
5.5 |
21.9 |
68.1 |
40/0.85 |
25.2 |
60.9 |
460 |
| 95 |
11.5 |
5.5 |
23.8 |
68.1 |
40/0.85 |
27.1 |
65.2 |
560 |
| 120 |
13.1 |
5.5 |
25.3 |
68.1 |
40/0.85 |
28.6 |
68.9 |
650 |
| 150 |
14.5 |
5.5 |
26.8 |
68.1 |
40/0.85 |
30.1 |
72.2 |
750 |
| 185 |
16.1 |
5.5 |
28.4 |
68.1 |
40/0.85 |
31.7 |
75.9 |
855 |
| 240 |
18.5 |
5.5 |
30.8 |
68.1 |
40/0.85 |
34.1 |
81.5 |
1060 |
| 300 |
20.7 |
5.5 |
33.2 |
68.1 |
40/0.85 |
36.7 |
87.5 |
1270 |
| 400 |
23.6 |
5.5 |
36.1 |
68.1 |
40/0.85 |
39.6 |
94.1 |
1570 |
| 500 |
26.5 |
5.5 |
39.0 |
68.1 |
40/0.85 |
42.5 |
100.8 |
1910 |
| Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
| 35 |
6.9 |
5.5 |
19.2 |
23.8 |
14/0.85 |
22.5 |
54.7 |
225 |
| 50 |
8.1 |
5.5 |
20.3 |
32.3 |
19/0.85 |
23.6 |
57.4 |
260 |
| 70 |
9.6 |
5.5 |
21.9 |
46.0 |
27/0.85 |
25.2 |
61.0 |
310 |
| 95 |
11.4 |
5.5 |
23.6 |
61.3 |
36/0.85 |
26.9 |
64.9 |
370 |
| 120 |
12.8 |
5.5 |
25.0 |
68.1 |
40/0.85 |
28.3 |
68.1 |
415 |
| 150 |
14.2 |
5.5 |
26.4 |
68.1 |
40/0.85 |
29.7 |
71.4 |
460 |
| 185 |
15.7 |
5.5 |
27.9 |
68.1 |
40/0.85 |
31.2 |
74.8 |
505 |
| 240 |
18.0 |
5.5 |
30.3 |
68.1 |
40/0.85 |
33.6 |
80.2 |
585 |
| 300 |
20.1 |
5.5 |
32.6 |
68.1 |
40/0.85 |
36.1 |
86.0 |
685 |
| 400 |
23.0 |
5.5 |
35.4 |
68.1 |
40/0.85 |
38.9 |
92.7 |
800 |
| 500 |
26.5 |
5.5 |
39.0 |
68.1 |
40/0.85 |
42.5 |
100.8 |
960 |
| Nom. Conductor Area |
Nom. Conductor Diameter |
Nom. Insulation Thickness |
Nom.Dia Over Insulation |
Nom.Screen Area on Each Core |
No.&Dia of Screen Wires |
Nominal Dia over Wire Screen |
Nom. Overall Diameter |
Approx. Weight |
| Nom. Conductor Area |
Nom. Conductor Diameter |
Nom. Insulation Thickness |
Nom.Dia Over Insulation |
Nom.Screen Area on Each Core |
No.&Dia of Screen Wires |
Nominal Dia over Wire Screen |
Nom. Overall Diameter |
Approx. Weight |
| Nom. Conductor Area |
Nom. Conductor Diameter |
Nom. Insulation Thickness |
Nom.Dia Over Insulation |
Nom.Screen Area on Each Core |
No.&Dia of Screen Wires |
Nominal Dia over Wire Screen |
Nom. Overall Diameter |
Approx. Weight |
| mm² |
mm |
mm |
mm |
mm2 |
No./mm |
mm |
mm |
kg/100m |
| Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
Copper Conductors,up to 10kA fault level |
| 50 |
8.0 |
8.0 |
25.5 |
49.4 |
29/0.85 |
28.8 |
69.4 |
460 |
| 70 |
9.6 |
8.0 |
27.1 |
68.1 |
40/0.85 |
30.4 |
73.0 |
560 |
| 95 |
11.5 |
8.0 |
29.0 |
68.1 |
40/0.85 |
32.3 |
77.3 |
665 |
| 120 |
13.1 |
8.0 |
30.6 |
68.1 |
40/0.85 |
33.9 |
81.1 |
765 |
| 150 |
14.5 |
8.0 |
32.0 |
68.1 |
40/0.85 |
35.5 |
84.8 |
875 |
| 185 |
16.1 |
8.0 |
33.6 |
68.1 |
40/0.85 |
37.1 |
88.4 |
990 |
| 240 |
18.5 |
8.0 |
36.0 |
68.1 |
40/0.85 |
39.5 |
94.1 |
1190 |
| 300 |
20.7 |
8.0 |
38.4 |
68.1 |
40/0.85 |
41.9 |
99.4 |
1410 |
| 400 |
23.6 |
8.0 |
41.3 |
68.1 |
40/0.85 |
44.8 |
106.2 |
1730 |
| 500 |
26.5 |
8.0 |
44.2 |
68.1 |
40/0.85 |
47.7 |
112.9 |
2070 |
| Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
Aluminum Conductors,up to 10kA fault level |
| 50 |
8.1 |
8.0 |
25.6 |
32.3 |
19/0.85 |
28.9 |
69.5 |
355 |
| 70 |
9.6 |
8.0 |
27.2 |
46.0 |
27/0.85 |
30.5 |
73.1 |
415 |
| 95 |
11.4 |
8.0 |
28.9 |
61.3 |
36/0.85 |
32.2 |
77.0 |
480 |
| 120 |
12.8 |
8.0 |
30.3 |
68.1 |
40/0.85 |
33.6 |
80.2 |
525 |
| 150 |
14.2 |
8.0 |
31.7 |
68.1 |
40/0.85 |
35.2 |
83.9 |
580 |
| 185 |
15.7 |
8.0 |
33.2 |
68.1 |
40/0.85 |
36.7 |
87.3 |
635 |
| 240 |
18.0 |
8.0 |
35.5 |
68.1 |
40/0.85 |
39.0 |
92.9 |
730 |
| 300 |
20.1 |
8.0 |
37.8 |
68.1 |
40/0.85 |
41.3 |
98.1 |
820 |
| 400 |
23.0 |
8.0 |
40.7 |
68.1 |
40/0.85 |
44.2 |
104.8 |
955 |
| 500 |
26.5 |
8.0 |
44.2 |
68.1 |
40/0.85 |
47.7 |
112.9 |
1120 |