Application:
Medium voltage Aerial Bundled Cables (MV-ABC), compliant with AS/NZS 3599.1, are designed for overhead reticulation in primary and secondary distribution networks, providing reliable feeders for residential and industrial service connections where space is constrained or bushfire risk is elevated.
Construction:

| Phase Conductor | Circular compacted stranded H68 aluminium |
| Conductor Screen | Extruded semi-conductive layer. |
| Insulation | XLPE. |
| Insulation Screen | Extruded semi-conductive layer. |
| metallic Screen(optional) | Copper wire screen or copper tape screen. |
| Separator | Semi-conductive swellable tape. |
| Outer Sheath | HDPE. |
| Support Conductor | Galvanized steel wires. |
| Assembly | Three XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay. |
Technical Parameters:
6.35/11 kV Al/XlPE /HDPE Non-Screened Cables
| NUMBER OF CORES X NOMINAL CROSS SECTION | PHASE CONDUCTOR | Messenger Suspension Unit | BREAKING LOAD | ||||
| DIAMETER OF CONDUCTOR | THICKNESS OF INSULATION | THICKNESS OF INSULATION SCREEN | THICKNESS OF SHEATH | STRANDING | NOMINAL SECTIONAL AREA | ||
| NO. ×MM² | MM | MM | MM | MM | NO. ×MM | MM² | KN |
| 3×35 | 6.9 | 3.4 | 0.8 | 1.2 | 7/4.75 | 52.4 | 1370 |
| 3×50 | 8.1 | 3.4 | 0.8 | 1.2 | 7/4.75 | 54.6 | 1530 |
| 3×70 | 9.7 | 3.4 | 0.8 | 1.2 | 7/4.75 | 57.8 | 1790 |
| 3×95 | 11.4 | 3.4 | 0.8 | 1.2 | 7/4.75 | 61.3 | 2100 |
| 3×120 | 12.8 | 3.4 | 0.8 | 1.2 | 19/3.50 | 67.3 | 2540 |
| 3×150 | 14.2 | 3.4 | 0.8 | 1.2 | 19/3.50 | 70.1 | 2840 |
| 3×185 | 15.7 | 3.4 | 0.8 | 1.2 | 19/3.50 | 73.1 | 3190 |
6.35/11 KV AL/XLPE/CWS/HDPE SCREENED CABLES
| NUMBER OF CORES X NOMINAL CROSS SECTION | DIAMETER OF CONDUCTOR | THICKNESS OF INSULATION | THICKNESS OF INSULATION SCREEN | COPPER WIRE SCREEN STRANDING | THICKNESS OF SHEATH | GALVANIZED STEEL WIRE STRANDING | NOMINAL SECTIONAL AREA | BREAKING LOAD |
| NO. ×MM² | MM | MM | MM | NO. ×MM | MM | NO. ×MM | MM² | KN |
| Light Duty Screen | ||||||||
| 3×35 | 6.9 | 3.4 | 0.8 | 25/0.85 | 1.8 | 7/2.00 | 54.1 | 1820 |
| 3×35 | 6.9 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 58.1 | 2130 |
| 3×50 | 8.1 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 60.4 | 2300 |
| 3×70 | 9.7 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 63.6 | 2570 |
| 3×95 | 11.4 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/200 | 67.0 | 2900 |
| 3×120 | 12.8 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 69.8 | 3190 |
| 3×150 | 14.2 | 3.4 | 0.8 | 25/0.85 | 1.9 | 19/200 | 73.0 | 3530 |
| 3×185 | 15.7 | 3.4 | 0.8 | 25/0.85 | 1.9 | 19/200 | 76.0 | 3890 |
| Heavy Duty Screen | ||||||||
| 3×35 | 6.9 | 3.4 | 0.8 | 40/0.85 | 1.8 | 7/2.00 | 54.1 | 2050 |
| 3×35 | 6.9 | 3.4 | 0.8 | 40/0.85 | 1.8 | 19/2.00 | 58.1 | 2360 |
| 3×50 | 8.1 | 3.4 | 0.8 | 23/1.35 | 1.8 | 19/2.00 | 62.4 | 2820 |
| 3×70 | 9.7 | 3.4 | 0.8 | 32/1.35 | 1.8 | 19/2.00 | 65.6 | 3440 |
| 3×95 | 11.4 | 3.4 | 0.8 | 39/1.35 | 1.8 | 19/2.00 | 69.0 | 4030 |
| 3×120 | 12.8 | 3.4 | 0.8 | 39/1.35 | 1.8 | 19/2.00 | 71.8 | 4320 |
| 3×150 | 14.2 | 3.4 | 0.8 | 39/1.35 | 1.9 | 19/2.00 | 75.0 | 4670 |
| 3×185 | 15.7 | 3.4 | 0.8 | 39/1.35 | 1.9 | 19/2.00 | 78.0 | 5020 |
12/7/22KV AL/XLPE/HDPE Non-Screened Cables
| NUMBER OF CORES X NOMINAL CROSS SECTION | PHASE CONDUCTOR | MESSENGER SUSPENSION UNIT STRANDING | NOMINAL SECTIONAL AREA | BREAKING LOAD | |||
| DIAMETER OF CONDUCTOR | THICKNESS OF INSULATION | THICKNESS OF INSULATION SCREEN | THICKNESS OF SHEATH | ||||
| NO. ×MM² | MM | MM | MM | MM | NO. ×MM | MM² | KN |
| 3×35 | 6.9 | 5.5 | 0.8 | 1.2 | 7/4.75 | 61.0 | 1780 |
| 3×50 | 8.1 | 5.5 | 0.8 | 1.2 | 7/4.75 | 63.3 | 1970 |
| 3×70 | 9.7 | 5.5 | 0.8 | 1.2 | 7/4.75 | 66.5 | 2260 |
| 3×95 | 11.4 | 5.5 | 0.8 | 1.2 | 7/4.75 | 69.9 | 2600 |
| 3×120 | 12.8 | 5.5 | 0.8 | 1.2 | 19/3.50 | 75.9 | 3070 |
| 3×150 | 14.2 | 5.5 | 0.8 | 1.2 | 19/3.50 | 78.7 | 3390 |
| 3×185 | 15.7 | 5.5 | 0.8 | 1.2 | 19/3.50 | 81.7 | 3760 |
12.7/22KV AL/XLPE/CWS/HDPE Screened Cables
| NUMBER OF CORES X NOMINAL CROSS SECTION | DIAMETER OF CONDUCTOR | THICKNESS OF INSULATION | THICKNESS OF INSULATION SCREEN | COPPER WIRE SCREEN | THICKNESS OF SHEATH | GALVANIZED STEEL WIRE STRANDING | NOMINAL SECTIONAL AREA | BREAKING LOAD |
| NO. ×MM² | MM | MM | MM | NO. ×MM | MM | NO.×MM | MM² | KN |
| Light Duty Screen | ||||||||
| 3×35 | 6.9 | 5.5 | 0.8 | 25/0.85 | 1.8 | 7/2.00 | 62.7 | 2280 |
| 3×35 | 6.9 | 5.5 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 66.7 | 2580 |
| 3×50 | 8.1 | 5.5 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 69.0 | 2780 |
| 3×70 | 9.7 | 5.5 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 72.6 | 3110 |
| 3×95 | 11.4 | 5.5 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 76.0 | 3460 |
| 3×120 | 12.8 | 5.5 | 0.8 | 25/0.85 | 2.0 | 19/2.00 | 79.2 | 3810 |
| 3×150 | 14.2 | 5.5 | 1.0 | 25/0.85 | 2.0 | 19/2.00 | 82.8 | 4230 |
| 3×185 | 15.7 | 5.5 | 1.0 | 25/0.85 | 2.1 | 19/2.00 | 86.2 | 4650 |
| Heavy Duty Screen | ||||||||
| 3×35 | 6.9 | 5.5 | 0.8 | 40/0.85 | 1.8 | 7/2.00 | 62.7 | 2510 |
| 3×35 | 6.9 | 5.5 | 0.8 | 40/0.85 | 1.8 | 19/2.00 | 66.7 | 2810 |
| 3×50 | 8.1 | 5.5 | 0.8 | 23/1.35 | 1.8 | 19/2.00 | 71.0 | 3300 |
| 3×70 | 9.7 | 5.5 | 0.8 | 32/1.35 | 1.9 | 19/2.00 | 74.6 | 3970 |
| 3×95 | 11.4 | 5.5 | 0.8 | 39/1.35 | 1.9 | 19/2.00 | 78.0 | 4600 |
| 3×120 | 12.8 | 5.5 | 0.8 | 39/1.35 | 2.0 | 19/2.00 | 81.2 | 4950 |
| 3×150 | 14.2 | 5.5 | 1.0 | 39/1.35 | 2.0 | 19/2.00 | 84.8 | 5360 |
| 3×185 | 15.7 | 5.5 | 1.0 | 39/1.35 | 2.1 | 19/2.00 | 88.2 | 5790 |
Our engineering team is ready to provide technical specifications, custom solutions, and competitive quotes.
Contact Sales →