Three Core Triplex 6.35-11–12.7-22kV

Home Products Three Core Triplex 6.35-11–12.7-22kV

Three Core Triplex 6.35-11–12.7-22kV

AS/NZS 1429.1 AS/NZS 1125 AS/NZS 3808
High-quality materials
International standards compliant
Durable construction
Long service life
Quality tested
Custom lengths available
Overview

Three Core Triplex 6.35-11–12.7-22kV

Application:

The main application of this highly specified Triplex cable is as a primary, high-reliability Medium Voltage (MV) feeder cable for underground power distribution networks, particularly in Australia and New Zealand where it conforms to AS/NZS 1429.1. It is designed to deliver three-phase power from main substations to local distribution points, or to supply power to major industrial, commercial, and utility sites.

Construction:

Conductor : Class 2 stranded(compacted) copper/Aluminum wire

Conductor screen : Semi-conductive compound material

Insulation: XLPE insulation –Colour: Natural

Insulation screen : Semi-conductive compound material

Binder tape :Semi-conductive water blocking binder tape

Metallic screen : HD-Plain anealed copper wire-(optional: LD)

Wrapping tape : Non-woven tape (Non-hygroscopic)

Outer Sheath : 5V-90 PVC (optional:HDPE/LSZH)-Colour: Black

Technical Parameters:

 6.35/11KV Triplex

Nominal
Conductor
Area
Nominal  Conductor
  Diameter
Nominal
Insulation
Thickness
Nominal
Diameter
Over Insulation
Nominal
Screen   Over Each Core
Min.No./Min Dia of Screen WiresNominal
Diameter
Over Wire
Screen
Nom.OD of
 Each Phase Cable
Nom.OD of TriplexAprox.
Mass
mm²mmmmmmmm²mo/mmmmmmmmkg/100m
Copper Conductors, up to 10kA fault level
164.83.412.815.928/0.8516.120.644.5165
255.83.413.824.443/0.8517.121.646.6220
356.83.414.834.424/13519.123.650.9280
508.03.416.048.734/13520324.853.4360
709.63.417.668.130/1.7022.627.158.4480
9511.53.419.468.748/13523.728360.9565
12013.13.421.068.748/13525.329.964.3650
15014.53.422.468.748/13526.731.567.8735
18516.13.424.168.748/13528.433.171.3830
24018.53.426.568.748/13530.835.777.01010
30020.73.428.968.748/13533.238.38251200
40023.63.431.868.748/13536341.68971480
50026.53.434.768.748/13539244.796.41780
Aluminum Conductors, up to 10kA fault level
356.93.414.922.740/0.8518.222.748.9180
508.13.416.032.923/13520.324.853.5230
709.63.417.645.832/1.721.926.457.0290
9511.43.419361.543/13523.628.260.7365
12012.83.420.768.748/13525.029.663.7415
15014.23.422.168.748/13526.431.267.2450
18515.73.423.668.748/13527.932.770.4485
24018.03.425.968.748/13530.235.275.8550
30020.13.428.368.748/13532.637.781.2615
40023.03.431.168.748/13535.641.088.3710
500       26.5      3434.768.748/13539.244.796.4840

12.7/22kV Triplex

Nominal
Conductor
Area
Nominal  Conductor
  Diameter
Nominal
Insulation
Thickness
Nominal
Diameter
Over Insulation
Nominal
Screen   Over Each Core
Min.No./Min Dia of Screen WiresNominal
Diameter
Over Wire
Screen
Nom.OD of
 Each Phase Cable
Nom.OD of TriplexAprox.
Mass
mm²mmmmmmmm²mo/mmmmmmmmkg/100m
Copper Conductors, up to 10kA fault level
35   6.8  5519.134.4   24/13523.4  28.0  60.2  35
50   8.0  5520.348.7   34/13524.6  29.1  62.7  405
70   9.6  5.521.968.7   48/135262  30.9  66.6  535
95   11.5  5.523.868.7   48/13528.1  32.8  70.7  620
120   13.1  5.525.368.7   48/13529.6  34.6  74.5  710
150   14.5  5526.868.7   48/13531.1  36.0  77.6  800
185   16.1  5528.468.7   48/13532.7  37.8  81.5  900
240   18.5  5530.868.7   48/13535.1  40.5  87.2  1080
300   20.7  5.533.268.7   48/13537.7  43.0  92.7  1280
400   23.6  5.536.168.7   48/13540.5  463  99.8  1570
500   26.5  5539.068.7   48/13543.5  492  105.1  1870
Aluminum Conductors, up to 10kA fault level
356.9  5519222.7  40/085   22.5   27.0   58.2225
508.1  5.520332.9  23/135   24.6   29.2   62.82万
709.6  5521.945.8  32/135   26.2   31.0   66.7345
9511.4  5523.B61.5  43/135   27.9   32.7   70.4420
12012.8  5.525.068.7  48/135   29.3   34.3   73.84万
15014.2  5.526.468.7  48/135   30.7   35.7   76.9510
18515.7  5.527.968.7  48/135   32.2   37.4   80.5550
24018.0  5530368.7  48/135   34.6   39.9   86.0620
30020.1  5532.668.7  48/135   37.1   42.4   91.4695
40023.0  5.535.468.7  48/135   39.9   45.7   98.4795
50026.5  5539.068.7  48/135   43.5   49.2  106.1930

6.35/11kV, URD Triplex

Aluminium Conductors,3kA Fault Level
Nominal
Conductor
Area
Nominal
Conductor
Diameter
Nominal
Insulation Thickness
Nominal Diameter Over InsulationNominal Screen Area on Each CoreNo&Nom. Dia of Screen WiresNominal Diameter Over Wire ScreenNominal Overall Diameter of Each Phase CableNominal Overall Diameter of TriplexApprox.
Mass
mm²mm  mmmm  mm²No./mmmmmmmmkg/100m
356.9  3.414.9  20.436/0.8518.222.748.9175
9511.4  3.419.3  20.436/0.8522.627.258.5250
18515.7  3.423.6  20.436/0.8526.931.768.2345
24018.0  3.425.9  20.436/0.8529.234.273.6410
30020.1  3.428.3  20.436/0.8531.636.779.1480

12.7/22kV URD Triplex

Aluminium Conductors,3kA Fault Level
Nominal
Conductor
Area
Nominal
Conductor
Diameter
Nominal
Insulation Thickness
Nominal Diameter Over InsulationNominal Screen Area on Each CoreNo&Nom. Dia of Screen WiresNominal Diameter Over Wire ScreenNominal Overall Diameter of Each Phase CableNominal Overall Diameter of TriplexApprox.
Mass
mm²mmmmmmmm²No./mmmmmmmmkg/100m
356.9619.220.436/0.8522.527.058.2220.0
9511.4623.620.43/0.8526.931.768.2305.0
18515.7627.920.436/0.8531.236.478.4415.0
24018.0630.320.436/0.8533.638.783.4480.0
Downloads

Documents & Certifications

Product DatasheetComing soon