Application:
0.6/1KV 3C+E SWA XLPE Orange Circular,manufactured as per AS/NZS5000.1, and its basic structure is CU/XLPE/SWA/PVC. The primary role of this cable is low-voltage power distribution where high mechanical protection is required.It is a heavy-duty solution for safely transmitting low-voltage power in environments where the cable must withstand physical stress, be buried, or run in exposed outdoor conditions.
Construction:
Conductor:Copper class 2 stranded /compacted as per AS/NZS 1125
Insulation: X-90 as per AS/NZS 3808
Bedding: Extruded PVC
Armour: Galvanized steel wire
Outer Sheath: PVC (5V-90)
Operating Temperature:90℃

| Nom.Cross Section | Approx.Diameter of Conductor | Thickness of Insulation | Diameter of Steel Wire Armour | Thickness of Outer Sheath | Approx.Overall Diameter | Conductor Resistance at 20℃ | Approx.Weight | |||
| Phase | Earth | Phase | Earth | Phase | Earth | |||||
| mm² | mm | mm | mm | mm | mm | mm | mm | Ω/km | kg/m | |
| 3C16+E6 | 5 | 3.09 | 0.7 | 0.7 | 1.25 | 1.8 | 23 | 1.15 | 3.08 | 1196 |
| 3C25+E6 | 6.1 | 3.09 | 0.9 | 0.7 | 1.6 | 1.8 | 26.4 | 0.727 | 3.08 | 1695 |
| 3C35+E10 | 7.1 | 4 | 0.9 | 0.7 | 1.6 | 1.8 | 28.8 | 0.524 | 1.83 | 2114 |
| 3C50+E16 | 8.4 | 5 | 1 | 0.7 | 1.6 | 1.9 | 32.3 | 0.387 | 1.15 | 2778 |
| 3C70+E25 | 10 | 6.1 | 1.1 | 0.9 | 2 | 2.1 | 38.1 | 0.268 | 0.727 | 3931 |
| 3C95+E25 | 12 | 6.1 | 1.1 | 0.9 | 2 | 2.2 | 42.5 | 0.193 | 0.727 | 4881 |
| 3C120+E35 | 13 | 7.1 | 1.2 | 0.9 | 2 | 2.3 | 45.5 | 0.153 | 0.524 | 5877 |
| 3C150+E50 | 14.9 | 8.4 | 1.4 | 1 | 2.5 | 2.5 | 52.3 | 0.124 | 0.387 | 7684 |
| 3C185+E70 | 16.5 | 10 | 1.6 | 1.1 | 2.5 | 2.6 | 57.2 | 0.0991 | 0.268 | 9257 |
| 3C240+E95 | 18.4 | 12 | 1.7 | 1.1 | 2.5 | 2.8 | 63 | 0.0754 | 0.193 | 11499 |
| 3C300+E120 | 21 | 13 | 1.8 | 1.2 | 2.5 | 3 | 69.2 | 0.0601 | 0.153 | 13918 |