Application:
0.6/1KV 2C+E XLPE Circular Orange Cable, primarily applied in buildings and industrial facilities where mechanical damage is not a concern. Compatible with indoor/outdoor deployment, and can be installed in enclosed conduits or underground ducts.
Construction:
Conductor : Class 2 stranded(compacted) copper wire
Insulation : X-90 XLPE (Red,Black,G/Y)
Filler: PP rope if needed
Binder tape: Non-hygroscopic woven tape
Outer Sheath : 5V-90 PVC(Orange,other colors available on request)

| Nom.Cross Section | Diameter of conductor | Thickness of Insulation | Thicknessof sheathLay up | Nominal OverallDia. | Approx.weight | Conductor Resistanceat 20℃ | |||
| Phase | Earth | Phase | Earth | Phase | Earth | ||||
| mm² | mm | mm | mm | mm | mm | mm | kg/m | Ω/km | |
| 2C1.5+E1.5 | 1.5 | 1.5 | 0.7 | 0.5 | 1.8 | 10.2 | 128 | 13.6 | 13.6 |
| 2C2.5+E2.5 | 2.01 | 2.01 | 0.7 | 0.6 | 1.8 | 11.4 | 171 | 7.41 | 741 |
| 2C4+E2.5 | 2.56 | 2.01 | 0.7 | 0.6 | 1.8 | 12.3 | 209 | 4.61 | 7.41 |
| 2C6+E2.5 | 3.09 | 2.01 | 0.7 | 0.6 | 1.8 | 13.2 | 257 | 3.08 | 741 |
| 2C10+E4 | 4 | 2.56 | 0.7 | 0.7 | 1.8 | 15.1 | 369 | 1.83 | 4.61 |
| 2C16+E6 | 5 | 3.09 | 0.7 | 0.7 | 1.8 | 17 | 522 | 1.15 | 3.08 |
| 2C25+E6 | 6.1 | 3.09 | 0.9 | 0.7 | 1.8 | 20.3 | 744 | 0.727 | 3.08 |
| 2C35+E10 | 7.1 | 4 | 0.9 | 0.7 | 1.8 | 22.1 | 988 | 0.524 | 1.83 |
| 2C50+E16 | 8.4 | 5 | 1 | 0.7 | 1.8 | 25.1 | 1367 | 0.387 | 1.15 |
| 2C70+E25 | 10 | 6.1 | 1.1 | 0.9 | 1.8 | 28.6 | 1879 | 0.268 | 0.727 |
| 2C95+E25 | 12 | 6.1 | 1.1 | 0.9 | 1.9 | 34 | 2455 | 0.193 | 0.727 |
| 2C120+E35 | 13 | 7.1 | 1.2 | 0.9 | 2 | 36.4 | 3062 | 0.153 | 0.524 |


Our engineering team is ready to provide technical specifications, custom solutions, and competitive quotes.